Natural ventilation performance for airborne diseases management in a deployable treatment facility

Published online by Cambridge University Press:  16 July 2026

Luca Fontana*
Affiliation:
Health Emergencies Programme, World Health Organization, Geneva, Switzerland
Gino Cortellessa
Affiliation:
Department of Civil and Mechanical Engineering, Universita degli Studi di Cassino e del Lazio Meridionale, Italy
Giorgio Grossi
Affiliation:
Department of Civil and Mechanical Engineering, Universita degli Studi di Cassino e del Lazio Meridionale, Italy
Anna Silenzi
Affiliation:
Health Emergencies Programme, World Health Organization, Geneva, Switzerland
Michele Di Marco
Affiliation:
Health Emergencies Programme, World Health Organization, Geneva, Switzerland
Antoine Chaillon
Affiliation:
Health Emergencies Programme, World Health Organization, Geneva, Switzerland
Robert Wunderlich
Affiliation:
University Department of Anesthesiology and Intensive Care Medicine, University Hospital Tübingen, Germany
Giorgio Buonanno
Affiliation:
Department of Civil and Mechanical Engineering, Universita degli Studi di Cassino e del Lazio Meridionale, Italy
*
Corresponding author: Luca Fontana; Email: fontanal@who.int
Rights & Permissions [Opens in a new window]

Abstract

Objective:

To assess whether wind-driven natural ventilation in the Infectious Diseases Treatment Module (IDTM) can achieve ventilation performance consistent with airborne precaution requirements [160 liters per second (L/s)] and to estimate associated pathogen-specific infection risks.

Methods:

An experimental campaign of air velocity measurements and CO2 decays were conducted to validate the developed computational fluid dynamics (CFD) model. The validated CFD model simulated wind-driven natural ventilation (1–4 m/s) for an L-shaped IDTM configuration under four structural scenarios defined by the presence or absence of patient porches and mosquito nets. Airborne infection risk was estimated using a Wells–Riley quanta-based model for seven representative airborne pathogens under short-duration healthcare worker exposure and prolonged patient co-exposure.

Results:

Ventilation performance varied widely based on wind speed and structural configuration. Airflow ranged from 7 L/s in the most restricted configuration (porch and mosquito nets present at 1 m/s) to over 3,100 L/s when mosquito nets were removed at 4 m/s.

When mapped to infection-risk estimates, ventilation rates at 160 L/s substantially reduced short-duration healthcare worker infection risk for all pathogens (≤1%), whereas prolonged co-exposure remained associated with high risk for high-emission pathogens despite high ventilation.

Conclusion:

Under favorable wind conditions and optimized configurations, the IDTM can achieve ventilation rates consistent with the 160 L/s recommendation for airborne precautions. While this provides substantial protection for healthcare workers, individual-room isolation remains essential for patient management. Operationally, removing window-mounted nets is the most effective way to ensure safety targets are met; hybrid ventilation measures should be considered during low-wind conditions.

Information

Type
Original Article
Copyright
© The Author(s), 2026. Published by Cambridge University Press on behalf of The Society for Healthcare Epidemiology of America
Figure 0

Figure 1.Figure 1 long description.Structural layout and key features of the Infectious Diseases Treatment Module (IDTM). The IDTM consists of three identical inflatable modules: one staff area (low-risk zone) positioned centrally and two patient-care modules (high-risk zone), each containing two individual 10 m2 patient rooms. The IDTM can be deployed in a longitudinal configuration (left) or in an L-shaped configuration (center), while maintaining staff visibility and workflow through the central low-risk zone. Each patient room includes five openable windows and a mosquito-net-equipped door, and each module features a patient porch area. Right: external view of the patient cabins and example of transparent monitoring screens that allow continuous patient observation from the staff area.

Figure 1

Figure 2.Numerical model setup. (a) computational domain and boundary conditions, (b) geometry of patient room highlighting the location of openable door and windows modeled as porous media to simulate mosquito nets, (c) detail of the computational mesh, selected for the CFD analysis, (d) detail of the three adopted computational meshes at an extrapolation plane height of 1.5 m.

Figure 2

Figure 3.Figure 3 long description.Wind-driven natural ventilation performance in the IDTM patient rooms across structural configurations. Wind-driven ventilation rates in the left and right IDTM patient rooms as a function of wind speed (1–4 m/s) under four structural configurations defined by the presence or absence of a patient porch and window-mounted mosquito nets. Ventilation is reported as volumetric airflow (L/s; left y-axis) with the corresponding air change rate (ACH, vol/h; right y-axis) for a 25 m3 room. Dashed horizontal reference lines indicate WHO airborne-precaution benchmarks: 160 L/s (red) and 12 ACH (blue). To facilitate comparison between rooms, the “Right room” panel includes ghosted (light gray) traces of the corresponding “Left room” results, highlighting the magnitude of the right–left ventilation deficit across wind speeds and configurations.

Figure 3

Figure 4.Infection risk as a function of ventilation rate in an IDTM patient room. Estimated infection risk (%) as a function of air changes per hour (ACH; 0.3–30 h‒1) and corresponding volumetric airflow (2.1–208.3 L/s) for seven airborne pathogens in a 10 m2 (25 m3) IDTM patient room, modeled using the Wells–Riley framework. Panel A shows the healthcare worker exposure scenario (15-min exposure following 60 min of patient presence). Panel B shows the patient co-exposure scenario (24-hr continuous exposure). The vertical lines indicate the WHO airborne precaution benchmarks: the 12 ACH target for mechanical ventilation (blue-dashed line) and the 160 L/s target for natural ventilation (red-dashed line). Risk is presented on a logarithmic scale.

Supplementary material: File

Fontana et al. supplementary material

Fontana et al. supplementary material