The mixing of airborne contaminants by the repeated passage of people along a corridor

Published online by Cambridge University Press:  02 October 2020

Nicola Mingotti
Affiliation:
BP Institute, University of Cambridge, Madingley Road, CambridgeCB3 0EZ, UK
Richard Wood
Affiliation:
BP Institute, University of Cambridge, Madingley Road, CambridgeCB3 0EZ, UK School of Civil Engineering, University of Leeds, Woodhouse Ln, LeedsLS2 9DY, UK
Catherine Noakes
Affiliation:
School of Civil Engineering, University of Leeds, Woodhouse Ln, LeedsLS2 9DY, UK
Andrew W. Woods*
Affiliation:
BP Institute, University of Cambridge, Madingley Road, CambridgeCB3 0EZ, UK
*
†Email address for correspondence: andy@bpi.cam.ac.uk

Abstract

We report a series of experiments in which a cylinder, with a vertical axis, is moved back and forth along a long narrow channel containing fresh water at Reynolds numbers $Re=3220\text {--}13\,102$. We examine the mixing of a cloud of dye along the channel by the oscillatory motion of the cylinder. Using light attenuation techniques to measure the time evolution of the concentration of dye along the channel, we find that at early times the concentration profile collapses to a Gaussian profile with dispersivity, $D=(2.4\pm 0.5) fdW$, where $f$ is the frequency of the cylinder oscillation, $d$ is the diameter of the cylinder and $W$ is the width of the channel, respectively. For times much longer than $L^2/D$, with $L$ being the length of the channel, the concentration becomes progressively more uniform over the whole length of the channel, and we show that the long-time non-uniform component decays with time dependence $\exp (- 4{\rm \pi} ^2 Dt / L^2)$. We consider the implications of these experiments for the dispersal of viral aerosols along poorly ventilated corridors, with implications for infection transmission in hospitals and public buildings.

Information

Type
JFM Papers
Creative Commons
Creative Common License - CCCreative Common License - BY
This is an Open Access article, distributed under the terms of the Creative Commons Attribution licence (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted re-use, distribution, and reproduction in any medium, provided the original work is properly cited.
Copyright
© The Author(s), 2020. Published by Cambridge University Press
Figure 0

Figure 1. Schematic representation of the experimental apparatus.

Figure 1

Table 1. Range of conditions for the experiments. $L$ (m) denotes the distance travelled by the cylinder along the channel, while $W$ (m) is the width of the channel. $d$ (m) is the diameter of the cylinder and $u$ (m s$^{-1}$) is its speed. $\hat {t}=t_t/(t_t+t_s)$ is the frequency of the oscillations of the cylinder (see § 5). $D$ (m$^2$ s$^{-1}$) is the estimate of the diffusion coefficient based on the early-time dispersal of the tracer in the tank, while $D_{\eta }$ (m$^2$ s$^{-1}$) is the estimate of the diffusion coefficient based on the late-time progressive homogenisation of the tracer concentration in the tank (see § 4). $Re=ud/{\nu }$ is the Reynolds number associated with the motion of the cylinder, with $\nu =1.0\times 10^{-6}$ m$^2$ s$^{-1}$ being the kinematic viscosity of water at the laboratory temperature 20 $^{\circ }$C.

Figure 2

Figure 2. (a) Series of images illustrating the dispersal of a pulse of dye during experiment k (see table 1). The images were captured at times 0, 16.3, 35.2, 45.9, 72.3 and 110.6 s after the beginning of the experiment. (b) For each image, false colours are used to illustrate the dye concentration field in the tank. (c) Time series of the vertically averaged profiles of dye concentration in the tank in experiments c, f and l (see table 1). In each time series image, the diagonal white line corresponds to the position of the cylinder at different times during the experiment.

Figure 3

Figure 3. (a) Coordinate of the centre of mass of the dyed fluid, $x_c$, as a function of time, $t$. $x_c$ has been estimated using (3.1). Data for experiments a–p (see table 1) are presented in dimensionless form: the coordinate of the centre of mass, $x_c$, is scaled by the length of the tank, $L$, while time $t$ is scaled by the time required for the cylinder to traverse the tank, $f^{-1}=L/u$.(b) Variance of the position of the dye pulse, $\sigma ^2$ (see (3.2)) at early times during the experiments. For clarity, only a selection of profiles have been plotted in this figure, while the collapse of all experimental results is presented in figure 5(b). (c) Root mean square deviation of the tracer concentration from the mean, $\eta$ (see (3.3)), at late times during the experiments. For clarity, only a selection of profiles have been plotted in this figure, while the collapse of all experimental results is presented in figure 7(b).

Figure 4

Figure 4. Effects of: (a) the speed of the cylinder, $u$; (b) the ratio of the width of the cylinder to that of the channel, $d/W$; and (c) the ratio of the width to the length of the channel, $W/L$, on the dispersivity of the tracer in the channel.

Figure 5

Figure 5. (a) Comparison of the values of $D$ estimated using (4.7) for experiments a–p (see table 1) with the values measured during the experiments; (b) illustration of the rescaled standard deviation of the tracer distribution at early times during experiments a–p (see table 1), as a function of the rescaled time.

Figure 6

Figure 6. (a) A series of 20 dye concentration profiles as measured at regular time intervals between times $t_1=10$ s and $t_2=70$ s during experiment m (see table 1) are collapsed using (4.10). The mean curve resulting from the average of the collapsed profiles is plotted using a dashed red line. (b) Comparison of the average collapsed profiles calculated for experiments a–p (see table 1). The profiles are compared with the Gaussian distribution plotted using (4.10) (red dashed line). It is seen that there is an error of less than 5 % between the averaged profiles and the Gaussian curve.

Figure 7

Figure 7. (a) The estimate of the diffusion coefficient $D$ (m$^2$ s$^{-1}$) obtained from the early-time variance data (experiments a–p in table 1, see figure 4) is compared with that obtained from the late-time data, $D_{\eta }$ (m$^2$ s$^{-1}$, see figure 3c and (4.12) and (4.13)). (b) Illustration of the rescaled profiles of root mean square deviation of tracer concentration from the mean, $\eta$ (see figure 2c). The collapse of the profiles from experiments a–p (see table 1) is plotted using (4.13).

Figure 8

Figure 8. (a) Time series of the vertically averaged profiles of dye concentration in the tank in four experiments with decreasing frequency of cylinder oscillation in the tank (experiments f, r, t and v, see table 1); (b) collapse of the standard deviation profiles of the tracer distribution in the channel using the rescaled diffusion coefficient given by (5.2) (experiments f and q–v, see table 1).