Clearing the air: Addressing air clearance times for infectious aerosols in healthcare facilities

Published online by Cambridge University Press:  24 August 2020

Andrew W. Hurlburt
Affiliation:
Divisions of Medical Microbiology and Infection Prevention, Vancouver Coastal Health, Vancouver, British Columbia
Rita J. DeKleer
Affiliation:
Divisions of Medical Microbiology and Infection Prevention, Vancouver Coastal Health, Vancouver, British Columbia
Elizabeth A. Bryce*
Affiliation:
Divisions of Medical Microbiology and Infection Prevention, Vancouver Coastal Health, Vancouver, British Columbia
*
Author for correspondence: Elizabeth Bryce, E-mail: Elizabeth.Bryce@vch.ca
Rights & Permissions [Opens in a new window]

Abstract

Information

Type
Letter to the Editor
Creative Commons
Creative Common License - CCCreative Common License - BY
This is an Open Access article, distributed under the terms of the Creative Commons Attribution licence (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted re-use, distribution, and reproduction in any medium, provided the original work is properly cited.
Copyright
© 2020 by The Society for Healthcare Epidemiology of America. All rights reserved
Figure 0

Fig. 1. Comparison of times required to clear particulates: The effect of air exchanges alone versus air exchanges and a relative humidity of between 40% to 60%. The following formula was used to estimate air clearance times (in minutes) for set Percent Particulate Removal Efficiencies (PRE) with changing Air Exchange Rates per hour (ACH) and both conservative (−30%) and moderate (−50%) reduction factors (RF) to account for a relative humidity (RH) of between 40 and 60%:$${\rm{t}} = - {{{\rm{In}}\left( {1 - ({\rm{PRE/100}}} \right))} \over {{\rm{ACH}}}} \times 60 \times {\rm{RF}}$$