Understanding the distribution of positive Legionella samples in healthcare-premise water systems: Using statistical analysis to determine a distribution for Legionella and to support sample size recommendations

Published online by Cambridge University Press:  08 October 2020

Dylan J. Nagy
Affiliation:
New York State Department of Health, Bureau of Water Supply Protection, Albany, New York School of Public Health, University at Albany, SUNY, Rensselaer, New York
David M. Dziewulski*
Affiliation:
New York State Department of Health, Bureau of Water Supply Protection, Albany, New York School of Public Health, University at Albany, SUNY, Rensselaer, New York
Neculai Codru
Affiliation:
New York State Department of Health, Bureau of Water Supply Protection, Albany, New York
Ursula L. Lauper
Affiliation:
New York State Department of Health, Bureau of Water Supply Protection, Albany, New York
*
Author for correspondence: David M. Dziewulski, E-mail: david.dziewulski@health.ny.gov
Rights & Permissions [Opens in a new window]

Abstract

Objective:

To significantly fit a statistical distribution to the proportion of positive Legionella samples in a series of water samples from multiple facility-premise water systems.

Design:

Statistical fit test.

Setting:

A hospital and associated long-term care facility (LTCF) in New York State, as well as temporal and culture data from a deidentified hospital site supplied by one of the vendor laboratories.

Methods:

Culture samples (n = 1,393) were segmented into 139 test cycles with roughly 10 samples in each. The proportion of positive samples was standardized to 25 total samples per test to give a distribution of discrete values. These values were analyzed for fit with the following discrete distributions: Poisson, negative binomial, geometric, and zero-inflated Poisson.

Results:

The zero-inflated Poisson distribution fitted to the copper–silver ionization (CSI)-treated and untreated test cycles indicates that 88% of the expected positive proportions should occur by the 30% cutoff (rounded up to 8 positive samples among 25 total samples), similar to the 93% expectation for just CSI-treated test cycles. The other treatment in these data (chlorine dioxide) was not effective in treating Legionella in the sampled buildings, and if there is an underlying distribution to these specific test cycles, it is not the zero-inflated Poisson distribution.

Conclusions:

In a well-maintained or well-treated premise water distribution system, ~30% or lower proportion of positive Legionella samples should occur. Anything above that cutoff is either very unlikely or not expected at all and indicates a problem in the water system.

Information

Type
Original Article
Copyright
© 2020 by The Society for Healthcare Epidemiology of America. All rights reserved.
Figure 0

Fig. 1. Observed proportion of tests (copper–silver ionization [CSI] treatment samples) and theoretical distributions. Plot of discrete adjusted observed proportions for CSI-treated test cycles (“sample”) with expected values from 4 tested discrete distributions. The expected values from the zero-inflated Poisson distribution were not significantly different from the adjusted observed values, suggesting that the proportion of samples positive for Legionella in a test cycle follows the zero-inflated Poisson distribution. , Sample; , Poisson; , Zero-inflated Poisson; , Negative Binomial; , Geometric.

Figure 1

Fig. 2. Cumulative distribution functions of observed positives and expectations. Plot of cumulative distribution functions for the zero-inflated Poisson distribution fit to the copper–silver ionization (CSI)-treated test cycles and the sample CSI-treated test cycles. The zero-inflated Poisson distribution suggests that ~93% of test cycles should be expected to have a positive sample proportion of ≤30%, and that 95% of test cycles should be expected to have a positive sample proportion of ≤36%. Values to the right of the red line (located at 8 positive samples among 25 tests on this graphic) indicate samples that fit the recommendation for interventions. The expectation (red transparent bars) for these test cycles are very low (<10%), reinforcing the hypothesis that these are unlikely results that may indicate a water system that is not behaving naturally. , Sample; , Zero-inflated Poisson.

Figure 2

Fig. 3. Comparison of observed positives with zero Poisson expectations. Plot of distribution of sampled test cycles for copper–silver ionization (CSI)-treated water and untreated water (minus four outliers among 95 total samples) with fitted zero-inflated Poisson distribution expected values. , Sample; , Zero-inflated Poisson.

Figure 3

Fig. 4. Comparison of observed positives with zero Poisson expectations. The zero-inflated Poisson distribution did not fit the distribution of positive samples among 25 tests for chlorine dioxide-treated water. , Sample; , Zero-inflated Poisson.

Supplementary material: File

Nagy et al. Supplementary Materials

Nagy et al. Supplementary Materials 1

Download Nagy et al. Supplementary Materials(File)
File 13.5 KB
Supplementary material: File

Nagy et al. Supplementary Materials

Nagy et al. Supplementary Materials 2

Download Nagy et al. Supplementary Materials(File)
File 2.2 MB