Hostname: page-component-7b7567c8c-2n9c9 Total loading time: 0 Render date: 2026-11-17T17:38:13.203Z Has data issue: false hasContentIssue false

Note on Losses in Cable Sheaths

Published online by Cambridge University Press:  24 October 2008

F. W. Carter
Affiliation:
St John's College
Rights & Permissions [Opens in a new window]

Extract

Core share and HTML view are not available for this content. However, as you have access to this content, a full PDF is available via the 'Save PDF' action button.

In a recent communication to the Society, the author referred to cable-sheath losses, and gave formulae for computing them in certain cases. These appertained to power cables in which were comprised a group of conductors, arranged symmetrically and encased in a single conducting sheath. In some distribution systems, however, the conductors for the several phases are encased in separate lead sheaths, which are either laid in proximity as separate cables, or grouped and comprehended in an outer sheath. The analysis previously given does not include such cases directly. Moreover, it is common practice either to lay the elementary cables with sheaths in contact, or to bond the sheaths together at the ends of suitable sections, in order to prevent differences of potential between them; and, when this is done, a circulating current flows in the circuit of the sheaths and bonds, sufficient to maintain equality of potential between the several sheaths. This current, to which reference was made in the former paper, is additional to the eddy current discussed therein, the integral of which over the cross section of the sheath is zero. It is for convenience here referred to as the “circulating current,” to distinguish it from the “eddy current,” although there is no such distinction between them as the names imply.

Information

Type
Research Article
Copyright
Copyright © Cambridge Philosophical Society 1928